| Technical Index | Specification |
| Input voltage | 1AC 220~240V±15% |
| 3AC 220~240V±15% |
| 3AC 380~460V±15% |
| Input frequency | 50/60Hz±5% |
| Output voltage | 0~rated input voltage |
| Output frequency | 0~6000Hz |
| Control mode | V/f control |
| Sensorless vector control |
| Torque control |
| Operation command mode | Keypad control |
| Terminal control |
| Serial communication control (Modbus) |
| Frequency setting mode | Digital setting, analog setting, pulse frequency setting, |
| serial communication setting, multi-step speed setting & |
| simple PLC, PID setting, etc. These frequency settings |
| can be combinated & switched in various modes. |
| Overload capacity | 150% / 120s, 160% / 60s, 180% / 10s, 200% / 1s. |
| Starting torque | 0.5Hz/180% (SVC); 1Hz/150% (V/f) |
| Speed control precision | ±0.5% (SVC) |
| Carrier frequency | 0.5~16.0kHz, automatically adjusted according to |
| temperature and load characteristics |
| Frequency accuracy | Digital setting: 0.01Hz |
| Analog setting: maximum frequency ×0.05% |
| Torque boost | Automatically torque boost; manually torque boost: |
| 0.1%~30.0% |
| V/f curve | Three types: linear, multiple point and square type |
| (1.2 power, 1.4 power, 1.6 power, 1.8 power, square) |
| Acceleration/deceleration mode | Straight line/S curve; four kinds of acceleration/deceleration |
| time, range: 0.0s~65000s |
| Braking unit | build-in standard. |
| DC braking | DC braking when starting and stopping |
| DC braking frequency: 0.0Hz~maximum frequency |
| Braking time: 0.0s~25.0s |
| Jog operation | Jog operation frequency: 0.0Hz~maximum frequency |
| Jog acceleration/deceleration time: 0.1s~3600.0s |
| Simple PLC & multi-step speed operation | It can realize a maximum of 16 multi-step speeds running via |
| the built-in PLC or control terminal. |
| Built-in PID | Built-in PID control to easily realize the close loop control of |
| the process parameters (such as pressure, temperature, |
| flow, etc.) |
| Automatic voltage regulation | Keep output voltage constant automatically when input |
| voltage fluctuating |
| Torque control | Torque control without PG |
| Wobble frequency control | Multiple triangular-wave frequency control, special for textile |
| Timing/length/ | Timing/length/counting control function |
| counting control |
| Over-voltage & over-current stall control | Limit current & voltage automatically during the running |
| process, prevent frequent over-current & over-voltage tripping |
| Fault protection function | Comprehensive protections include over-current, over- |
| voltage, under-voltage, overheating, default phase, |
| overload, shortcut, etc., can record the detailed running |
| data while failures happen. |
| Input terminals | Programmable digital input: 7 multifunctional inputs, one can be work as high speed pulse input. |
| 3 programmable analog input: |
| AI1, AI2, AI3: 0~10V / 4~20mA |
| Output terminals | 2 relay outputs, |
| 2 open collector outputs, |
| 2 anaalog outputs, 0~10V / 4~20mA |
| Communication terminals | Build-in standard RS485 communication interface, support |
| MODBUS-RTU communication protocol |
| LED display | Display frequency setting, output frequency, output voltage, |
| output current, etc. Two lines display |
| Ambient temperature | -10~50°C, without direct sunshine. |
| Humidity | 90%RH or less (non-condensing) |
| Altitude | ≤1000M: output rated power, >1000M: output derated |
| Storage temperature | -20~60°C |